Features | Unit | ATV1124 |
Air flow rate (free blow) | m³/h | 26 |
Flow rate with exit filter | m³/h | 15 |
Power supply | V/Hz | 24 DC |
Dimensions HxLxP | mm | 114x114x60 |
Power consumption | W | 4 |
Current consumption | A | 0.16 |
Overcurrent consumption | - | impedance |
Electric connection | - | 2-poles spring terminals |
Duty cycle | - | 100% |
Operating temperature | °C | - 10 / +70 (+14 / +158) |
Protection degree/class | - | IP54/Class I |
Noise level | dB(A) | 35 |
Flow direction | - | reversible: default factory setting outside-in |
Bearing | - | ball |
Filter mat (Eurovent) | - | G2 |
Service life (at 40°C) | hr | 50 000 |
Material | - | ABS UL94V-0 Color RAL7035 |
Wall thickness | mm | 1.2-2.4 |
Gasket | - | foam seal gasket |
Weight (with packaging) | kg | 0.20 (0.25) |
Package dimensions | mm | 125x125x80 |
Montaggio | - | fast clip-on |
Conformity/Approvals | - | CE |
Accessories | ||
Fan speed controller | - | |
Hood for IP56 | - | |
Thermostat 0-60°C – NO contact | THV2 |